Specification Guidelines: Allan Block Modular Segmental Wall Systems |
Download: .PDF
.DOC
|
The following specifications provide Allan Block Corporation's typical requirements
and recommendations. At the engineer of record's discretion these specifications may
be revised to accommodate site specific design requirements.
|
SECTION 1
PART 1: GENERAL
|
|
1.1 Scope
|
Work includes furnishing and installing modular concrete block retaining wall
units to the lines and grades designated on the construction drawings and as
specified herein.
|
|
1.2 Applicable Sections of Related Work
|
Section 2: Geogrid Wall Reinforcement
|
|
1.3 Reference Standards
|
-
ASTM C1372 Standard Specification for Segmental Retaining Wall Units.
-
ASTM C1262 Evaluating the Freeze thaw Durability of Manufactured CMU’s
and Related concrete Units
-
ASTM D698 Moisture Density Relationship for Soils, Standard Method
-
ASTM D422 Gradation of Soils
-
ASTM C140 Sample and Testing concrete Masonry Units
|
|
1.4 Delivery, Storage, and Handling
|
-
Contractor shall check the materials upon delivery to assure
proper material has been received.
-
Contractor shall prevent excessive mud, cementitious material,
and like construction debris from coming in contact with the materials.
-
Contractor shall protect the materials from damage. Damaged material shall
not be incorporated in the project (ASTM C1372).
|
PART 2: MATERIALS
|
|
2.1 Modular Wall Units
|
-
Wall units shall be Allan Block Retaining Wall units as produced by
a licensed manufacturer.
-
Wall units shall have minimum 28 day compressive strength of 3000 psi
(20.7 MPa) in accordance with ASTM C1372. The concrete units shall have
adequate freeze-thaw protection with an average absorption rate in accordance
with ASTM C1372 or an average absorption rate of 7.5 lb/ft3 (120 kg/m3) for
northern climates and 10 lb/ft3 (160 kg/m3) for southern climates.
-
Exterior dimensions shall be uniform and consistent. Maximum dimensional
deviations on the height of any two units shall be 0.125 in. (3 mm).
-
Wall units shall provide a minimum of 110 lbs total weight per square foot
of wall face area (555 kg/m2). Fill contained within the units may be
considered 80% effective weight.
-
Exterior face shall be textured. Color as specified by owner.
|

Figure 1: Standard AB Unit - Approximate Dimensions
|
|
|
2.2 Wall Rock
|
-
Material must be well-graded compactable aggregate, 0.25 in. to 1.5 in.,
(6 mm - 38 mm) with no more than 10% passing the #200 sieve. (ASTM D422)
-
Material behind and within the blocks may be the same material.
|
|
2.3 Infill Soil
|
-
Infill material shall be site excavated soils when approved by the
on-site soils engineer unless otherwise specified in the drawings.
Unsuitable soils for backfill (heavy clays or organic soils) shall not
be used in the reinforced soil mass. Fine grained cohesive soils (φ<31)
may be used in wall construction, but additional backfilling, compaction
and water management efforts are required. Poorly graded sands, expansive
clays and/or soils with a plasticity index (PI) >20 or a liquid limit (LL)
>40 should not be used in wall construction.
-
The infill soil used must meet or exceed the designed friction angle
and description noted on the design cross sections, and must be free
of debris and consist of one of the following inorganic USCS soil types:
GP, GW, SW, SP meeting the following gradation as determined in accordance
with ASTM D422.
|
| Sieve Size |
Percent Passing |
4 inch (100 mm) |
100 – 75 |
No. 4 (4.75 mm) |
100 – 20 |
No. 40 (0.425 mm) |
0 - 60 |
No. 200 (0.075 mm) |
0 - 35 |
|
-
Where additional fill is required, contractor shall submit sample
and specifications to the wall design engineer or the onsite soils
engineer for approval and the approving engineer must certify that
the soils proposed for use has properties meeting or exceeding
original design standards.
|
PART 3: WALL CONSTRUCTION
|
|
3.1 Excavation
|
-
Contractor shall excavate to the lines and grades shown on the
construction drawings. Contractor shall use caution not to over-excavate
beyond the lines shown, or to disturb the base elevations beyond those shown.
-
Contractor shall verify locations of existing structures and utilities
prior to excavation. Contractor shall ensure all surrounding structures are
protected from the effects of wall excavation.
|
|
3.2 Foundation Soil Preparation
|
-
Foundation soil shall be defined as any soils located beneath a wall.
-
Foundation soil shall be excavated as dimensioned on the plans and
compacted to a minimum of 95% of Standard Proctor (ASTM D698) prior to
placement of the base material.
-
Foundation soil shall be examined by the on-site soils engineer to ensure
that the actual foundation soil strength meets or exceeds assumed design
strength. Soil not meeting the required strength shall be removed and replaced
with acceptable material.
|
|
3.3 Base
|
-
The base material shall be the same as the Wall Rock material
(Section 2.2) or a low permeable granular material.
-
Base material shall be placed as shown on the construction drawing.
Top of base shall be located to allow bottom wall units to be buried
to proper depths as per wall heights and specifications.
-
Base material shall be installed on undisturbed native soils or suitable
replacement fills compacted to a minimum of 95% Standard Proctor (ASTM D698).
-
Base shall be compacted at 95% Standard Proctor (ASTM D698) to provide a
level hard surface on which to place the first course of blocks. The base
shall be constructed to ensure proper wall embedment and the final elevation
shown on the plans. Well-graded sand can be used to smooth the top 1/2 in.
(13 mm) on the base material.
-
Base material shall be a 4 in. (100 mm) minimum depth for walls under 4 ft
(1.2 m) and a 6 in. (150 mm) minimum depth for walls over 4 ft (1.2 m).
|
|
3.4 Unit Installation
|
-
The first course of wall units shall be placed on the prepared base with
the raised lip facing up and out and the front edges tight together.
The units shall be checked for level and alignment as they are placed.
-
Ensure that units are in full contact with base. Proper care shall be
taken to develop straight lines and smooth curves on base course as per wall
layout.
-
Fill all cores and cavities and a minimum of 12 in. (300 mm) behind the
base course with wall rock. Use infill soils behind the wall rock and
approved soils in front of the base course to firmly lock in place. Check
again for level and alignment. Use a plate compactor to consolidate the
area behind the base course. All excess material shall be swept from top
of units.
-
Install next course of wall units on top of base course. Position blocks
to be offset from seams of blocks below. Perfect "running bond" is not
essential, but a 3 in. (75 mm) minimum offset is recommended. Check each
block for proper alignment and level. Fill all cavities in and around wall
units and to a minimum of 12 in. (300 mm) depth behind block with wall
rock. For taller wall application the depth of wall rock behind the block
should be increased; walls from 15 ft (4.57 m) to 25 ft (7.62 m) should have
a minimum of 2 ft (0.61 m) and walls above 25 ft (7.62 m) should have a
minimum of 3 ft (0.9 m). Spread infill soil in uniform lifts not exceeding
8 in. (200 mm) in uncompacted thickness and compact to 95% of Standard
Proctor (ASTM D698) behind the consolidation zone.
|

Figure 2: Consolidation Zone - Gravity Wall
|
-
The consolidation zone shall be defined as 3 ft (0.9 m) behind the wall.
Compaction within the consolidation zone shall be accomplished by using a
hand operated plate compactor and shall begin by running the plate compactor
directly on the block and then compacting in parallel paths from the wall
face until the entire consolidation zone has been compacted. A minimum of
two passes of the plate compactor are required with maximum lifts of 8 in.
(200 mm). Expansive or fine-grained soils may require additional compaction
passes and/or specific compaction equipment such as a sheepsfoot roller.
Maximum lifts of 4 inches (100 mm) may be required to achieve adequate
compaction within the consolidation zone. Employ methods using lightweight
compaction equipment that will not disrupt the stability or batter of the
wall. Final compaction requirements in the consolidation zone shall be
established by the engineer of record.
-
Install each subsequent course in like manner. Repeat procedure to the
extent of wall height.
-
As with any construction work, some deviation from construction drawing
alignments will occur. Variability in construction of SRWs is approximately
equal to that of cast-in-place concrete retaining walls. As opposed to
cast-in-place concrete walls, alignment of SRWs can be simply corrected or
modified during construction. Based upon examination of numerous completed
SRWs, the following recommended minimum tolerances can be achieved with good
construction techniques.
-
Vertical Control - ±1.25 in. (32 mm) max. over 10 ft
3 m) distance
-
Horizontal Location Control - straight lines ±1.25 in.
(32 mm) over a 10 ft (3 m) distance.
-
Rotation - from established plan wall batter: 2.0°
-
Bulging - 1.0 in. (25 mm) over a 10 ft (3.0 m) distance
|
|
3.5 Additional Construction Notes
|
-
When one wall branches into two terraced walls, it is important to note that
the soil behind the lower wall is also the foundation soil beneath the upper
wall. This soil shall be compacted to a minimum of 95% of Standard Proctor
(ASTM D698) prior to placement of the base material. Achieving proper compaction
in the soil beneath an upper terrace prevents settlement and deformation of the
upper wall. One way is to replace the soil with wall rock and compact in 8 in.
(200 mm) lifts. When using on-site soils, compact in maximum lifts of 4 in.
(100 mm) or as required to achieve specified compaction.
-
Filter fabric use is not suggested for use with cohesive soils.
Clogging of such fabric creates unacceptable hydrostatic pressures
in soil reinforced structures. When filtration is deemed necessary
in cohesive soils, use a three dimensional filtration system of
clean sand or filtration aggregate.
|
-
Embankment protection fabric is used to stabilize rip rap and
foundation soils in water applications and to separate infill
materials from the retained soils. This fabric should permit the
passage of fines to preclude clogging of the material. Embankment
protection fabric shall be a high strength polypropylene monofilament
material designed to meet or exceed typical Corps of Engineers
plastic filter fabric specifications (CW-02215); stabilized against
ultraviolet (UV) degradation and typically exceeding the values in
Table 1, page 8 of the AB Spec Book.
|
|
|
-
Water management is of extreme concern during and after construction.
Steps must be taken to ensure that drain pipes are properly installed and
vented to daylight and a grading plan has been developed that routes water
away from the retaining wall location. Site water management is required both
during construction of the wall and after completion of construction.
|
|